CODEAPPLICATIONS BY MARK C. ODE
Proper installation and maintenance
ensure transfer switches function correctly and the generator starts when it
needs to. However, many electricians and
electrical contractors know only what
is in the National Electrical Code (NEC),
such as the information on transfer
switches in Article 700 covering emergency power, Article 701 covering legally
required standby power, and Article 702
for optional standby power. The listing and
labeling information for these devices contains many more requirements, and the
electrician and contractor must understand them to enable a proper installation.
Underwriters Laboratories’ 2015
Guide Information for Electrical Equipment, normally called 2015 UL White
Book, contains important information
pertinent to electrical designers, installers, inspectors and engineers. Within the
guide, Category WPTZ covers transfer
switches, which can have a maximum
rating of 600 volts (V) alternating current
(AC), can be automatic or nonautomatic,
and can have associated control devices.
Transfer equipment can also be rated in
excess of 600V AC but cannot exceed 38
kilovolts.
If a normal supply fails, automatic-transfer switches are intended to transfer
a common load to an alternate supply.
They also are intended to automatically
return the load to the normal supply
when the normal supply source is re-
established. Transfer switches rated for
total system transfer (100 percent load
transfer) are marked, “Suitable for con-
trol of motors, electric discharge lamps,
tungsten filament lamps, and electric
heating equipment where the sum of
motor full-load ampere ratings and the
ampere rating of other loads do not
exceed the ampere rating of the switch
and the tungsten load does not exceed
____ percent of the switch rating.” The
manufacturer would fill in the blank
with the percentage value based on the
switch’s continuous rating.
Transfer switches have been investigated for load switching and in-rush
capabilities as well as the number of
operation cycles based on the switches’
intended use, which includes scheduled test operations where the full load
is switched. Most transfer switches are
designed so the load cannot be simultaneously disconnected from both normal and
alternate-power sources where either
power source is available. The exception
is if the transfer switch is suitable for use
as service equipment and the disconnecting means is externally accessible so
each power source (service or other) can
be independently disconnected. Transfer
switches that are rated for use as service
equipment may be provided with ground-fault protection as part of the transfer
switch and may contain feeder overcurrent protective devices.
Transfer switches are typically
intended for use with copper conduc-
tors, unless marked to indicate terminals
that are suitable for use with aluminum
conductors. This additional marking for
aluminum conductors is independent
of any marking on the terminal connec-
tors and is indicated on a wiring diagram
or other readily visible location. This
requirement is different from most other
electrical equipment because it requires
a specific marking on the switch or on
the wiring diagram indicating alumi-
num conductors can be used. Unless
marked otherwise, wiring space within
the switch enclosure and the termina-
tions is based on 60°C wire for switches
rated 100 amperes (A) or less and 75°C
for switches rated more than 100A.
Transfer switches that contain integral overcurrent devices are suitable for
continuous loads at 100 percent of the
switch-rated current, unless restricted
to not more than 80 percent of rated
load current. The switch will be clearly
marked as “Continuous Load Current
Not to Exceed 80% of Switch Rating.” If
the transfer switch does not contain integral overcurrent-protective devices, the
transfer switch is rated at 100 percent of
rated current.
Most transfer switches are not permitted to be installed on the line side of
the service overcurrent device and must
be marked with the maximum ampere
and class of fuse. If a circuit breaker is
used for protection, the switch manufacturer must provide the breaker’s specific
size, specific manufacturer and maximum current rating.
Transfer switches may be required to
be marked as follows: “When protected
by a circuit breaker rated no more than
____ amperes, this transfer switch is rated
for use on a circuit capable of delivering
not more than 10 kA rms symmetrical
amperes, ____ volts maximum.” The first
blank is filled with the circuit breaker’s
maximum current rating, and the second
is filled with the maximum circuit voltage.
There is much to know about transfer
switches in addition to the information
that the NEC contains.
Pass the Source
The important aspects of transfer switches
TRANSFER SWITCHES are the unsung and often neglected heroes of emergency,
legally required standby and optional standby systems. The much larger generators
and other alternate-power sources often overshadow these switches, but ultimately,
these devices sense normal power loss and activate the generator or alternate power
source to critical loads.
OD E is a lead engineering instructor at Underwriters Laboratories Inc., based in Peoria, Ariz.
He can be reached at 919.949.2576 and mark.c.ode@us.ul.com. I S T
O
C
K